In a Pt100, lead resistance becomes error — 1 Ω is about 2.6 °C. 2-, 3- and 4-wire, tolerance classes, thermocouple types K to B, cold-junction compensation.

Process temperature sensors come in two main kinds: resistance temperature detectors (RTDs, typically Pt100) and thermocouples. An RTD measures a platinum resistance that changes with temperature; a thermocouple measures the thermoelectric voltage (mV) at the junction of two different metals. The resistance and voltage values below are calculated from the IEC 60751 equation and the NIST ITS-90 thermocouple tables (SRD 60).

Pt100: 100 Ω at 0 °C

TemperaturePt100 resistance
−200 °C18.52 Ω
−100 °C60.26 Ω
0 °C100.00 Ω
100 °C138.51 Ω
200 °C175.86 Ω
400 °C247.09 Ω
850 °C390.48 Ω

Near 0 °C the resistance changes by about 0.39 Ω per °C (IEC 60751, α = 0.00385), so a 0.39 Ω resistance error is about a 1 °C temperature error. A Pt1000 follows the same equation with ten times the resistance.

2-wire, 3-wire and 4-wire

ConnectionWhat is measuredEffect of lead resistance
2-wireSensor plus both leads togetherAdded in full — reads high
3-wireA third lead measures lead resistance to subtract itCancelled when all three leads are equal
4-wireSeparate current leads and voltage-sensing leadsNegligible — almost no current in the sensing leads

With 1 Ω of total lead resistance on a 2-wire connection, a Pt100 reads about 2.6 °C high at 0 °C and a Pt1000 about 0.26 °C. Longer and thinner leads have more resistance, so 2-wire suits short runs or Pt1000. 3-wire cancels only when the three leads match in length, gauge and contact resistance; a loose terminal or a splice to a different gauge leaves an error. For higher accuracy use 4-wire.

Start from what the receiving input (temperature controller, transmitter) accepts. To connect a 2-wire sensor to a 3-wire input, follow the terminal instructions in the input's manual.

Tolerance classes (IEC 60751)

IEC 60751 grades the sensor's own tolerance. Class A is ±(0.15 + 0.002·|t|) °C and class B ±(0.3 + 0.005·|t|) °C — ±0.15 °C and ±0.3 °C at 0 °C, ±0.35 °C and ±0.8 °C at 100 °C. A tighter class AA and a looser class C also exist. Each class is valid over its own temperature range, different for wire-wound and thin-film elements, so check the sensor datasheet. The class covers the sensor; 2-wire lead error comes on top.

Thermocouple types

TypeMaterials (+ / −)NIST table rangeEMF at 100 °C
KNickel-chromium / nickel-aluminum−270 to 1372 °C4.096 mV
JIron / copper-nickel−210 to 1200 °C5.269 mV
TCopper / copper-nickel−270 to 400 °C4.279 mV
ENickel-chromium / copper-nickel−270 to 1000 °C6.319 mV
NNicrosil / nisil−270 to 1300 °C2.774 mV
RPlatinum-13% rhodium / platinum−50 to 1768.1 °C0.647 mV
SPlatinum-10% rhodium / platinum−50 to 1768.1 °C0.646 mV
BPlatinum-30% rhodium / platinum-6% rhodium0 to 1820 °C0.033 mV

The NIST range is where the EMF equations are defined. The usable upper limit is lower depending on wire gauge and sheath, so follow the sensor maker's specification.

What to consider when choosing

Cold-junction compensation

A thermocouple's mV depends on the temperature difference between the measuring tip and the input terminals (the cold junction). NIST tables assume a 0 °C cold junction, so the instrument measures its terminal temperature and adds the corresponding voltage. Example: measuring 300 °C with type K and terminals at 25 °C gives 11.208 mV. Looking that up as if the cold junction were 0 °C gives about 275.8 °C — some 24 °C low.